V100E Fail Freeze Positioner
Brand: Valve Accessories & ControlsBy adding the Fail Freeze module to the base pneumatic valve positioner, you convert this product to an electronic “fail in place” positioner. While under normal function, this unit operates as a normal 4-20 mA positioner.
However, should you have a power interruption, the special unit will “lock” the actuator in place and “fail freeze” the package at its last signal position. Once power is restored, the unit will regain its original normal operation.
Features- Compact Design
- Quality components = rugged and accurate performance
- Screwdriver slots in the span and zero ferrules, along with external zero adjustments, helps make +calibrating the positioner simple
- Easily maintain all key components
- Clear, visible indicator with arrow indicator standard-beacon optional
- Field changeable to any I/p option
Specifications
Input Range
- 4-20 mA
- Load presents 6 volts (± 0.5 V) constant voltage drop to the current source
Supply Pressure
- 22 - 100 psi (0.15 - 1 MPa)
Linearity Error
- < 1.0 % Full Scale
Hysteresis
- < 0.5 % Full Scale
Repeatability
- < 0.5 % Full Scale
Temperature Range
- -20° to 150° F (-20° to 66° C)
Weight
- 6 lbs (2.65 kg)
Spool/Pilot Valves
- Low Bleed/Low Gain
- Standard
- High Gain
Air Delivery
- @ 29 psi (200 kPa): 9.5 scfm (270 slpm)
- @ 87 psi (600 kPa): 28.3 scfm (800 slpm)
Air Consumption
- @ 29 psi: 0.2 scfm (5.7 slpm)
- @ 87 psi: 0.6 scfm (17 slpm)
Bleed Rate at 87 psi (600 kPa)
- Low Bleed/Low Gain: 0.4 scfm
- Standard: 0.53 scfm
- High Gain: 0.70 scfm
Pressure Gain
- Low Bleed/Low Gain: 300:1
- Standard: 750:1
- High Gain: 1000:1
Air Connections
- 1/4” NPT or G Threads
Gauges
- 1/8” NPT or G Threads
Cable Entry
- 1/2” NPT
- Optional 30 mm square Connector DIN 43650
Ingress & Corrosion Protection
- NEMA 4X & IP65
Standard Coating
- Powder Polyester
Supply Pressure Effect
- 0.25 psig per 25 psig supply change
Loop Voltage Drop
- 7 V Max. @ 20 mA
Reverse Protection
- 250 mA
Overcurrent Protection
- 250 mA
Fail Freeze Mode
- Input signal fail below 3.5 mA
Fail Freeze Drift Rate
- 2 % per hour max
Documentation
Brochure
Product Guide
- External I/P Wiring pdf 94 KB
- Fail Freeze Orientation/Sensitivity Statement pdf 180 KB
- Spindle Drawings pdf 281 KB
- V100 Declaration of Conformity pdf 578 KB
- V100E-FF Dimensional Drawing pdf 143 KB
- V100E-FF Ordering Codes pdf 233 KB
- V100E-FF Principle of Operation pdf 2.0 MB
- V100E-FF Spare Parts pdf 504 KB
- V100E-FF Technical Specs pdf 1.3 MB