Q46H/65 Chlorine Dioxide
Brand: Analytical Technology IncQ46H/65 monitors use a polarographic membraned sensor to accurately measure ClO2 in water.
The sensor operates much like a battery, generating current that is linearly proportional to the concentration of chlorine dioxide in solution.
A ClO2 permeable membrane isolates the sensor from the measured sample and insures that the measurement is interference free.
Two versions of the sensor are available, a sensor intended for installation in a flowcell and a sensor intended for submersion applications.
Requiring minimal maintenance, sensors are easy to use and easy to maintain.
An integral RTD provides temperature compensation and allows temperature to be displayed and transmitted from the monitor.
Features- pH Input Option
- Programmable range options from 0-200 PPB
up to 0-200 PPM provide maximum application flexibility - AC or DC Power Options
- Analog Output Options
- PID Output
- Digital Communications. Available for either Profibus-DP,
Modbus-RTU, or Ethernet-IP - Relay Contacts
- Flexible Mounting
- Back-lit large LCD display provides clear visibility in any lighting conditions. A scrolling second line on the display provides additional information and programming prompts.
Specifications
Display Range
- 0-200 PPB, 0-2.000, 0-20.00 or 0-200.0 ppm
Accuracy
- 0.5 % of Selected Range or 0.02 ppm
Repeatability
- 0.3 % of Selected Range or 0.01 ppm
Non-Linearity
- 0.1 % of Selected Range
Temperature
- 0.01 % of Span/°C
Power
- 100-240 Vac, ± 10 %, 50/60 Hz,10 VA Max.
- 12-24 Vdc, 500 mA Max.
Analog Outputs
- Two Isolated 4-20 mA, 500 Ω load Max. (3rd Output Optional)
Relays
- Three SPDT, 6A @ 250 Vac, 5A @ 24 Vdc (3 Additional SPST Non-Isolated, 1A @ 30 Vdc Optional)
Display
- 4 Digit, 0.75” Numeric LCD with 12 Character Second Line, LED Back Light.
Enclosure
- NEMA 4X (IP-66) Polycarbonate, V-0 Flammability
Operating Temperature
- -20° to 60° C (-4° to 140° F)
Weight
- 6 lbs (2.7 kg) with Sensor, Flowcell & Accessories
Zero Drift
- < 0.01 ppm/Month
Sensor
- Membraned-Covered Amperometric (Polargraphic)
Sensor Materials
- PVC & 316SS
Sensor Response Time
- 90 % in 60 Seconds
Sensor Temperature Limits
- 0° to 50° C
Sensor Pressure Limit
- 0-50 psig
Sensor Cable
- 25 ft (7.5 m) Standard
Sensor Flowcell
- Clear Acrylic Constant-Head Overflow Standard Sealed Acrylic Flowcell Optional
Sensor Sample Connections
- 1/4” I.D. Hose Barb Inlet
- 1/2” I.D. Hose Barb Drain for Standard Flowcell
Temperature Sensor
- Internal Pt100 RTD
- Food Washing
- Pulp and Paper Mill
- Cooling Water
- Potable Water Treatment